pdficon

Download
Datasheet

Shortform Catalogue



Hazardous
Zone 1 RMS 560
Industrial
Zone 2 RMS 550




Industrial


Site Map

<

RMS 550

RMS 550-Em

aqua_ex.jpgThe RMS 550 range of zone 2 fluorescent luminaires is manufactured from AISI304 stainless steel. The body is fabricated from a single sheet of steel with no invasive mounting holes to minimize the risk of water ingress through the housing. The tempered glass window minimizes the risk of light output loss over time due to poly-carbonate yellowing. The RMS range is ideally suited for on and offshore and marine environments and all kinds of industry where there is a high level of corrosion.

Specification
Material Stainless Steel AISI 304/AISI316 , 0.8 mm thickness and transparent part in tempered glass
IP Rating IP66
Temperature -30°C to 55°C
Approvals Atex-INERIS 01ATEX3002X & GOST
Standards

EN/IEC: 60079-0, 60079-15 & EN: 61241-0, 61241-1

Ex-code Atex II 3 GD
Ex nA II T5 Tamb. -30°C to 50°C
Ex nA II T4 Tamb -30°C to 55°C
Ex tD A22 T90° Tamb -30°C to 40°C
Ex tD A22 IP66/67 T100° Tamb -30°C to 50°C
Ex tD A22 IP66/67 T105° Tamb -30°C to 55°C
According to European Directive 94/9/EC (ATEX)For Zone 2 and Zone 22
Gaskets Special cross section tightness gasket, silicon rubber made (close cells) located in housing channel between body and window frame.
Entries Body complete of two diam. 21mm through holes for cable entries, one complete of metallic plug with lock nut and gasket, and the other one with plastic plug for dust protection.
Hardware and Screw

AISI 304 Stainless Steel external hardware and screws

Lamps

RMS Series is suitable for two pins fuorescent lamps G13 socket PHILIPS TL-D or equivalent.(lamps excluded) - 18 / 36 W

Ballast High-frequency electronic ballast
conforming with EN 60079-15 & IEC 60079-15
Power Supply 220-240 Volts AC 50 ÷ 60 Hz Power factor> 0.95
Accessories
Available upon request
Suspension mounting kit "G1" AISI 304 made
Pole mounting kit "P12" 1 ½" size AISI 304 made
Wall mounting kit "H1" AISI 304 made
Emergency Service RMS 550 lighting fxtures for Emergency Service are available:RMS 550...PNL/LE-P
Note Very low pollution at the end of operative life time of lighting fxtures.
The inorganic materials used for RMS, like stainless steel and glass, allow a recycle of 95%, only electrical components and insulation of single core wires need some more care.
No through holes between inside and outside of luminaries, out of holes for power supply cable whatever protected by a suitable waterproof cable gland (on request). Therefore, during the time, release would be possible where, for fxing devices, there are through holes and relevant gaskets.